Unical 100 kW (Condensing)
Orders are accepted via WhatsApp
Modulation ratio 1:5
Nominal heating power Qn kW 99.5 at low calorific value
Minimum heating power Qmin kW 20 at low calorific value
Rated useful power (Tbr. 30/Tpod. at 50 °C) Pcond kW 105
Minimum useful power (Tbr. 30/Tpod. at 50 °C) Pcond min kW 21.75
Efficiency at maximum power (at Tbr. 60/Ts. 80°C) % 97.1
Efficiency at 30% power (at Tbr 30°C) % 109.3
Exhaust gas temperature T.otx. gases – T. environment environment (maximum) °C 39.4
Maximum operating temperature °C 85
Maximum allowed temperature °C 100
The minimum pressure in the heating circuit bar is 0.5
Maximum pressure in the bar of the heating circuit 6
Water content l 9
Max. condensate output kg/h 8.46
CO 140 at minimum heat output with 0% O2 mg/kWh
NOx 0% O2 mg/kWh 47 at nominal heating capacity
Power supply voltage/Frequency V/Hz 230/50
Power supply fuse A(R) 4
Electrical protection level IP X5D
Weight kg 96